Emergency lighting is separate from your EICR, but it is checked on a similar cycle and is often booked in the same visit. The standard to follow is BS 5266-1.
Monthly functional test
Once a month, each emergency light should be switched to battery for a short time to confirm it lights. This is often done by the site team using a test key, and the result is recorded in the log book.
Annual full-duration test
Once a year, the system is run on battery for its full rated duration, usually three hours, to confirm the batteries can still support it. Lights that fail are repaired or replaced and retested.
Records and responsibility
- Keep a log book with the date and result of every test.
- The responsible person under the Regulatory Reform (Fire Safety) Order 2005 must make sure the system is maintained.
- Your fire risk assessment should reference the emergency lighting records.
Combining it with your EICR
The annual duration test can be scheduled alongside your EICR, so the building only has one disruption window and one set of contractors on site.