An Electrical Installation Condition Report (EICR) lists everything the inspector found, and each finding is given a code. The codes decide whether the report is satisfactory and how quickly anything needs to be fixed, so it pays to understand them before the remedial quote arrives.
C1: danger present
A C1 means there is a risk of injury right now, such as exposed live parts that can be touched. The inspector should make it safe on the day, usually by isolating the circuit, and tell the person responsible straight away. Any C1 makes the report unsatisfactory.
C2: potentially dangerous
A C2 is not dangerous this minute, but could become so if a fault occurred. Typical examples are missing main protective bonding or no RCD protection where it is required. C2 items need urgent remedial work, and any C2 makes the report unsatisfactory.
C3: improvement recommended
C3 items do not meet the current edition of BS 7671 but are not considered dangerous. They do not make the report unsatisfactory. You can budget for them separately rather than treating them as urgent.
FI: further investigation
FI means the inspector found something that needs more investigation than the inspection allowed, for example an unexpected test result on a circuit that could not be traced. FI items should be investigated without delay and, like C1 and C2, they make the report unsatisfactory.
What to do with a coded report
- Ask for an itemised remedial quote that lists each C1, C2 and FI item separately.
- Keep the C3 recommendations on file and plan them into future maintenance.
- Once the work is done, keep the certificates for each repair with the original report.